Close

Welcome to the SKALN Customer Portal, where our customers can view and download useful information such as MSDS's. If you would like to open an account, please contact us.

Close


Super Insulating Oil GXI

 

Product Description: SKALN Transformer Super insulating oil GXI adopts special refined mineral oil with low content of sulfur and electric insulating oil with antioxidant. SKALN Transformer Supe

 

Super Insulating Oil GXI

Super Insulating Oil GXI

Product Description:

  1. SKALN Transformer Super insulating oil GXI adopts special refined mineral oil with low content of sulfur and electric insulating oil with antioxidant.
  2. SKALN Transformer Super insulating oil GXI is in accordance with accepted industry and the new standard of copper corrosion test.

Product performance:

* Good electric insulativity can prevent electric field from discharging efficiently.

* Long service life.

* Give protection to transfer.

* Improve the efficiency. The good low-temperature property can make sure the transfer exchanges heat normally even under the low temperature.

* Good anti-oxidation stabilitycan prevent from forming the acidic substances and sludge efficiently.

* Good thermal conductivitycan make the core and windings of transformer keep cooling.

Product Specification:

Apply to the transformer under 330V voltage level and electrical equipment with similar requirements.It can used as insulation cooling medium.

Use in High voltage application.

Product Application:

Many kinds of transformers (like generator transformer, mutual inductor, distribution transformer and so on) and UHVDC power transmission substation.

Electronic equipment.

Rectifier, circuit breaker, Casing, inductive transformer and switch.

High voltage application.

Product Parameter:

SKALN Transformer Super insulating oil GXI

Iterm

45

Test method

Density,(20℃),kg/m3

878.9

GB/T1884

Knematic viscosity,mm2/s,40℃

8.606

GB/T265

Pour point, ℃

<-45

GB/T3535

Flash point(open cup), ℃

144

GB/T261

neutralization value,mgKOH/G

<0.01

GB/T264

breakdown voltage,( Interval of 2.5 mm out of the stone),KV

70

GB/T507

dielectric loss factor,(90 ℃)

<0.001

GB/T5654

interfacial tension,Mn/M

49

GB/T6541

Moisture,mg/kg

20.5

SH/T0207

Analysis capability,UI/min

+2

GB/T11142